1U Liquid Cooling Module
1. General Information
The 1U Liquid Cooling Module (Server Level Sealed Loop) cooler replaces the less efficient air coolers and enables air-cooled data centers to utilize the highest performing CPUs and GPUs. The superior cooling characteristics of the liquid cooler enables server LSL to capture more heat and transfer it into the air
This product specification covers all components in the cooler
1.1 Basic Specifications
Specification |
Value |
SKU Number |
|
SKU Description |
|
Storage Temperatures |
-16°C to 70°C |
Operating Liquid Temperature |
2° to 60°C |
Operating Air Temperature |
25°C cold aisle intake |
Cold Plate |
|
Material |
Copper |
Thermal Resistance |
RCP,case = 0.1 K/W |
MTTF |
> 50000 Hours(operation temperature: 250C) |
2. LGA4677 1U Liquid Cooling Module
This Server Level Sealed Loop cooler includes the pump and cold plate with an integrated liquid-to- air heat exchanger to cool one CPU. The server cooler is
delivered as a complete, prefilled assembly. No need for OEMs or Data Centers to handle the server coolant
2.1 Basic Components
This Server LSL cooler consist of the following elements:
1. Cold plate assembly
2. Pump
3. Liquid-to-air heat exchanger
4. Server coolant (inside server cooler)
5. Tube
The server coolers are delivered fully assembled as shown above and filled with server coolant.
2.2 Pump Specification
1U Liquid Cooling Module is provided with water cooling by one water pump, and 3 PIN(2510) terminal, LGA 4677 socket provides tachometer
signal for the pump to monitor the operation of the pump
SPECIFICATION |
VALUE |
Pump connect Type |
3PIN(2510) |
Socket Type |
LGA 4677 |
Pump Information |
Flow: > 2.0l/min; Lift: ≥ 3.5m |
Pump Operating Temperature |
2~450C |
Pump Bearing Type |
Ceramic bearing |
Pump Shaft Type |
Ceramic shaft |
Pump Speed, at full power & 100% PWM |
3100~4000 RPM |
Starting Current |
2A |
Starting Voltage |
6V |
Pump Housing Material |
PPS+ GF40 |
Pump Housing Flammability Rating |
V-0 (UL 94 Requirements) |
Stall Protection |
Auto-restart at 3-10 second intervals |
Noise |
< 43 dB |
Stator Type |
8 pole, Three phase sensorless motor driver |
Solt Type |
6 Solts |
Direction of Rotation |
Counter-clockwise |
Cold Plate |
|
Material |
Copper T2 |
Cold Plate Mechanical |
|
Length |
118 mm |
Width |
78 mm |
Height |
27mm |
Weight (inc. liquid) |
1180g ( Total product net weight) |
Retention Nuts |
K37251/K37295 |
Electrical |
|
Rated Voltage |
12 VDC |
Operating Voltage |
10.8 – 13.2 VDC |
Minimum Startup Voltage |
6.0 VDC |
Rated Current |
0.5A—0.7 A |
Rated Power |
6W—8.4W |
Electrical Connection |
Pin1: FG Pin2: PWR 12V Pin3: GND |
Pump Cable Wire Gauge |
UL2468 24 AWG |
Power Cable Length (pump to connector) |
320 mm |
Pump Speed |
FG signal |
Pump Speed Control (via PWM signal) |
Disabled |
Working Fluid |
|
Coolant |
20% glycol+80% purified water |
2.3 Liquid Tube Specification
The tubes are designed to transport the coolant between the different components inside the server.
2.4 Server Liquid Coolant Specification
The coolant is a mixture of 80% demineralized water and% 20 glycol
Specification |
Value |
Hazards identification |
This product is not classified as dangerous according to EC or ROSH criteria. |
EC Classification |
This product does not require classification according to the criteria of the Commission of the European Communities. |
Heat transfer fluid |
Glycol volume ratio 20% |
Liquid coolant content |
Approximately 180 g |
2.5 1U Liquid Cooling Module heat exchanger specification
The Heat Exchanger is specifically used to fit with the LGA4677 cooler.
Specification |
Value |
Material |
Aluminum |
Dimensions |
|
Length |
243.5mm core, 274 mm exterior |
Width |
64 mm core,73 exterior |
Depth |
35.5 mm core, 40 mm exterior (ex barbs) |
Fin Pitch |
3.2/mm |
Color |
Painted: Pantone Black 7C |
2.6 Manifold and flow resistance
Specification |
Value |
Material |
Fluororubber(FKM) |
Dimensions(mm) |
|
Length |
60.0 |
Width |
40.6 |
Depth |
4.5 |
Color |
Black |
Operating temperature |
-50C ~ 150 0C |
Water pressure resistance |
1.35l/Min (Tested by cooling head) |
2.7 Compliance with Standards
SPECIFICATION |
VALUE |
Safety |
IEC/EN/UL 62368-1 |
Environmental |
· IEC60068: ENVIRONMENTAL TESTING · Meets ISTA standards for packaging · IEC 60068-2-27, 1987 Tests: Test Ea and guidance: Shock · IEC 60068-2-29, 1987 Tests: Test Eb and guidance: Bump · IEC 600721-3, 1984 Classification of groups of environmental parameters and their severities · IEC 60068-2-6, 1995: Test Fc, Vibration sinusoidal · IEC 60068-2-64, 1993: Test Fh: vibration, broad-band Random (digital control) and guidance · RoHS directive 2002/95/EC for Toxicity and Hazardous Substances (EN/DIN 62321: 2006-07) · Reach · UL (C and US) · CE · CA Prop 65 · Halogen Free |
Shock & Vibrations |
· Meets ISTA standards for packaging · IEC 60068-2-27, 1987 Tests: Test Ea and guidance: Shock · IEC 60068-2-29, 1987 Tests: Test Eb and guidance: Bump · IEC 60068-2-6, 1995: Test Fc, Vibration sinusoidal · IEC 60068-2-64, 1993: Test Fh: vibration, broad-band Random (digital control) and guidance |
EMC |
Tested according to following standards: · EN 61000-4-2 Magnetic Discharge · EN 61000-4-3 RF Field Immunity · EN 61000-4-4 Burst, Fast transients · EN 61000-4-6 RF Conducted Immunity · EN 61000-4-8 Magnetic field 50/60 Hz · EN55022/CISPR22 RF Field Emission · FCC CLASS A |
2.8 Packaging
Specification |
Value |
Shipping box |
|
- Product unit net weight |
1.2KG |
- Units per shipping box |
5 |
- Inner packing tory ( 1 unit) |
350 x 300 x 60mm |
- Dimensions of shipping box (LxWxH) |
370mm x 320mm x 325mm |
- Gross weight per box incl. goods |
8.5kg |
Palletization |
|
- Shipping boxes per pallet |
36 |
- Pallet size (LxWxH) |
1250mm x 1000mm x 120mm |
- Dimensions of loaded pallet (LxWxH)) |
1250mm x 1000mm x 1800mm |
- Gross weight (not including pallet) |
525 kg |